Investigations Into the Stray Gassing of Oils in the Fault Diagnosis of Transformers
- 6 May 2014
- journal article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Power Delivery
- Vol. 29 (5) , 2369-2374
Abstract
In this paper, we present an analysis of the gases generated by mineral oil and cellulose transformer insulation, at temperatures lower than those expected to be caused by an actual thermal fault. Gassing at relatively low temperatures, 100 ° C to 200 ° C, often presents a problem to the asset manager since it can be difficult to distinguish this event from that caused by an actual fault. Previous stray gassing tests were only performed for 164 h, at two temperatures, and two oxygen contents. We tested a mineral oil under 20 different conditions of oxygen and water content, for up to nearly 100 days. We found that at low-temperature levels and that by using high oxygen levels, the generation of ethylene can be more significant when compared to the other hydrocarbon gases than first thought.Keywords
This publication has 5 references indexed in Scilit:
- Ageing rate of paper insulation used in power transformers Part 2: Oil/paper system with medium and high oxygen concentrationIEEE Transactions on Dielectrics and Electrical Insulation, 2012
- Ageing rate of paper insulation used in power transformers Part 1: Oil/paper system with low oxygen concentrationIEEE Transactions on Dielectrics and Electrical Insulation, 2012
- Unusual ethylene production of in-service transformer oil at low temperatureIEEE Transactions on Dielectrics and Electrical Insulation, 2012
- A Thermodynamic Approach to Evaluation of the Severity of Transformer FaultsIEEE Transactions on Power Delivery, 2011
- A review of faults detectable by gas-in-oil analysis in transformersIEEE Electrical Insulation Magazine, 2002