An Analytically Defined Fire‐Suppressing Foam Formulation for Evaluation of Fluorosurfactant Replacement
Authors:
- 31 July 2018
- journal article
- research article
- Published by Wiley in Journal of Surfactants and Detergents
- Vol. 21 (5) , 711-722
Abstract
A 4‐component, analytically defined, reference fluorosurfactant formulation (Ref‐aqueous film forming foam [AFFF]) composed of 0.3% fluorocarbon‐surfactant concentrate (Capstone 1157), 0.2% hydrocarbon‐surfactant concentrate (Glucopon 215 UP), and 0.5% diethylene glycol mono butyl ether by volume in distilled water was found to have rapid fire extinction comparable to a commercial AFFF in tests conducted on a bench scale and a large scale (28 ft2, part of US Military Specification, MIL‐F‐24385F). The Ref‐AFFF was analytically characterized to provide the identity and quantity of the chemical structures of the surfactant molecules that were lacking for commercial AFFF formulations. To arrive at an acceptable Ref‐AFFF formulation, 3 candidate formulations containing different hydrocarbon surfactants in varying amounts were evaluated and ranked relative to a commercial AFFF using a bench‐scale fire‐extinction apparatus; varying the hydrocarbon surfactant was found to affect the fire‐extinction time. The ranking was confirmed by the large‐scale tests suggesting that the bench‐scale apparatus is a reasonable research tool for identifying surfactants likely to succeed in the large‐scale test. In the future, replacing the fluorocarbon surfactant with an alternative surfactant in the Ref‐AFFF enables a direct comparison of fire extinction and environmental impact to identify an acceptable fluorine‐free formulation.Keywords
Funding Information
- Strategic Environmental Research and Development Program (SERDP) (WP2739)
This publication has 15 references indexed in Scilit:
- Influence of fuel on foam degradation for fluorinated and fluorine-free foamsColloids and Surfaces A: Physicochemical and Engineering Aspects, 2017
- Surface Cooling of a Pool Fire by Aqueous FoamsCombustion Science and Technology, 2016
- Fluoro- vs hydrocarbon surfactants: Why do they differ in wetting performance?Advances in Colloid and Interface Science, 2014
- The structure of the fire fighting foam surfactant Forafac®1157 and its biological and photolytic transformation productsChemosphere, 2012
- Fire‐Fighting Foam Technology2012
- The search for alternative aqueous film forming foams (AFFF) with a low environmental impact: Physiological and transcriptomic effects of two Forafac® fluorosurfactants in turbotAquatic Toxicology, 2011
- New Additive for Low Viscosity of AFFF/AR Concentrates—Study of the Potential Fire PerformanceFire Technology, 2004
- Fluorinated surfactants: synthesis, properties, effluent treatmentJournal of Fluorine Chemistry, 2002
- Perfluorinated Surfactants and the Environmental Implications of Their Use in Fire-Fighting FoamsEnvironmental Science & Technology, 2000