Analysis of the Temperature Non-Uniformity of the Rotor Winding of a Powerful Air-Cooled Turbogenerator

Authors:

Abstract
This research paper presents results of applying Conjugate Heat Transfer method (CHT) for heat transfer and fluid flow modeling of the rotor turns temperature field with self-ventilation from sub-slot and radial channels in the air-cooled turbogenerator of maximum power in order to predict thermal behavior and to define possible constrains. The computational modeling presented in the research takes into account the crucial input data of the rotor generator and air flow during process of cooling. The particular focus of this paper is the temperature non-uniformity investigation the of the turns in the different configurations. The analysis of these properties was made it possible to find the patterns of formation and characteristic qualities of the temperature field and, accordingly, the resulting thermomechanical consequences. The potential of improving the thermal utilization of a rotor design is shown.
Funding Information
  • Russian Foundation for Basic Research