Comparison of different methods available for evaluating remaining life of OIP insulation used in power transformers
- 1 October 2017
- conference paper
- Published by Institute of Electrical and Electronics Engineers (IEEE)
- p. 209-214
Abstract
This paper provides an analysis of various methods for estimating the remaining life of in-service power transformer. Degree of Polymerization (DP) value is perhaps the most effective parameter for determining the remaining life of an Oil-Impregnated-Paper insulation system. Due to the invasive nature of the test, DP value determination using paper samples is not practically feasible for in-situ transformers. On the other hand, commercial equipment's make it relatively easy to obtain the values of paper-moisture and tanδ. Hence, these parameters have become popular among utilities. In the present paper, paper-moisture and tanδ are used to obtain several important dielectric properties (like tensile strength, Degree of Polymerization, hotspot temperature) which are subsequently used for estimating the remaining life of several real-life power transformers. Efforts are also made to identify the method which is capable of identifying remaining life of power transformer with minimum error.Keywords
This publication has 9 references indexed in Scilit:
- Aging Assessment of Power Transformer Using Multi-parametersInternational Journal on Electrical Engineering and Informatics, 2013
- Ageing rate of paper insulation used in power transformers Part 2: Oil/paper system with medium and high oxygen concentrationIEEE Transactions on Dielectrics and Electrical Insulation, 2012
- Prediction of Transformer Insulation Life with an Effect of Environmental VariablesInternational Journal of Computer Applications, 2012
- Investigation of Polarization and Depolarization Current for Evaluation of Moisture in Oil-Pressboard InsulationInternational Journal of Computer and Electrical Engineering, 2011
- Moisture determination and degradation of solid insulation system of power transformers2010
- Aging Study and Lifetime Estimation of Transformer Mineral OilAmerican Journal of Engineering and Applied Sciences, 2008
- Review of modern diagnostic techniques for assessing insulation condition in aged transformersIEEE Transactions on Dielectrics and Electrical Insulation, 2003
- Insulation thermal life considerations for transformer loading guidesIEEE Transactions on Power Delivery, 1992
- A review of paper aging in power transformersIEE Proceedings C Generation, Transmission and Distribution, 1985