New algorithm for the protection of delta‐hexagonal phase shifting transformer
Authors:
Open Access
- 1 January 2014
- journal article
- research article
- Published by Institution of Engineering and Technology (IET) in IET Generation, Transmission & Distribution
- Vol. 8 (1) , 178-186
Abstract
Delta/hexagonal phase shifting transformer (PST) represents both magnetically coupled and electrically connected circuits, which makes it unique in design and construction from a standard transformer. Conventionally, differential protection serves as a main protection element of PST and offers distinguished features such as speed and selectivity. On the contrary, it is prone to various new challenges in addition to well‐recognised traditional ones when applied to delta/hexagonal PST. New challenges include non‐standard phase shift between two ends, saturation of the series winding, dependence of differential/restraining currents on tap changer position and turn–turn fault detection. This study exploits the unique design of PST and explores the suitability of applying electromagnetic equations by presenting a new algorithm for the protection of PST. In addition to the internal/external fault detection and discrimination capability, unlike differential protection, the proposed algorithm remains stable during magnetisation inrush current, current transformer saturation and saturation of the series winding. Even though the implementation of the proposed algorithm requires currents, voltages and tracking of the tap‐changer position, capabilities of the algorithm make it a distinguished and unique protection solution. Performance of the algorithm is tested and analysed for various fault and non‐faulted power system conditions using power systems computer aided design/electromagnetic transient including DC (PSCAD/EMTDC) software.Keywords
This publication has 13 references indexed in Scilit:
- Use of Standard 87T Differential Protection for Special Three-Phase Power Transformers—Part I: TheoryIEEE Transactions on Power Delivery, 2012
- Computer Relaying for Power Systems2009
- Modeling and Protection of Hexagonal Phase-Shifting Transformers—Part I: Short-Circuit ModelIEEE Transactions on Power Delivery, 2008
- Modeling and Protection of Hexagonal Phase-Shifting Transformers—Part II: ProtectionIEEE Transactions on Power Delivery, 2008
- Universal Adaptive Differential Protection for Regulating TransformersIEEE Transactions on Power Delivery, 2008
- Protective Relaying2006
- A wavelet-based technique for discrimination between faults and magnetizing inrush currents in transformersIEEE Transactions on Power Delivery, 2003
- A digital relaying algorithm for detecting transformer winding faultsIEEE Transactions on Power Delivery, 1989
- Digital protection method for power transformers based on an equivalent circuit composed of inverse inductanceIEEE Transactions on Power Delivery, 1988
- A New Computer-Based Flux-Restrained Current-Differential Relay for Power Transformer ProtectionIEEE Transactions on Power Apparatus and Systems, 1983