Abstract
This paper describes a method for estimating the additional aging in medium/low voltage distribution transformers caused by increasing demand from electric vehicle charging. The proposed method combines detailed travel demand data from the National Household Transportation Survey with a one-year model of transformer hottest spot temperature, based on on IEEE C57.91-1995 Annex G. To illustrate the the model outputs, we present results for 15kVA and 25kVA overhead distribution transformers using ambient temperatures from Burlington, VT and Los Angeles, CA. Our results illustrate the importance of ambient temperatures to impact of PEVs on transformer aging.Keywords
This publication has 14 references indexed in Scilit:
- Technical Challenges of Plug-In Hybrid Electric Vehicles and Impacts to the US Power System: Distribution System Analysis2010
- Challenges of PHEV penetration to the residential distribution network2009
- Green Market Geography: The Spatial Clustering of Hybrid Vehicles and LEED Registered BuildingsThe B.E. Journal of Economic Analysis & Policy, 2009
- Emissions Impacts and Benefits of Plug-In Hybrid Electric Vehicles and Vehicle-to-Grid ServicesEnvironmental Science & Technology, 2009
- Life Cycle Assessment of Greenhouse Gas Emissions from Plug-in Hybrid Vehicles: Implications for PolicyEnvironmental Science & Technology, 2008
- Potential Impacts of Plug-in Hybrid Electric Vehicles on Regional Power Generation2008
- Using Global Positioning System Travel Data to Assess Real-World Energy Use of Plug-In Hybrid Electric VehiclesTransportation Research Record: Journal of the Transportation Research Board, 2007
- Evaluation of Utility System Impacts and Benefits of Optimally Dispatched Plug-In Hybrid Electric Vehicles (Revised)2006
- Vehicle-to-grid power fundamentals: Calculating capacity and net revenueJournal of Power Sources, 2005
- Temperature Rise of an Oil-Filled Transformer with Varying LoadIEEE Transactions on Power Apparatus and Systems, 1984