Experiments on Convection Heat Transfer Along a Vertical Flat Plate Between Pools with Different Temperatures

Authors:

Abstract
To evaluate the heat removal capability of an external water wall-type containment vessel, which is a passive system for containment cooling, thermal-hydraulic behavior in the suppression and outer pools has been examined experimentally. The following results are obtained: A thermal stratification boundary, which separates the pools into an upper high-temperature region and a lower low-temperature region, is observed just below the vent outlet.The natural-convection heat transfer coefficients (HTCs) for the downward and upward flows that appear inside and outside the primary containment vessel wall are measured. These values can be expressed by Nu = 0.13Ra1/3.The condensation HTCs in the presence of non-condensable gas, which affect heat transfer between the wet well and the outer pool, are measured along the long wall. The vertical variations of the condensation HTCs are within 10% of the averaged coefficients, and the averaged coefficients can be expressed by hm = 0.43(ma/ms)-0.8, where hm (kW/m...