The Setting Map Methodology for Adjusting the DG Anti-Islanding Protection Considering Multiple Events
- 15 March 2018
- journal article
- research article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Power Delivery
- Vol. 33 (6) , 2755-2764
Abstract
This paper proposes a simple and practical methodology to adjust the pick-up and time-delay settings of passive anti-islanding protection commonly used in distributed generation point of common coupling: underfrequency/overfrequency, rate of change of frequency, vector surge, and undervoltage/overvoltage. The proposed methodology, called setting map, provides a graphical approach that helps define the most suitable settings for the passive anti-islanding protection to, simultaneously, maximize the islanding detection capability and minimize incorrect trips due to events other than islanding. Based on that, the methodology also contains an automatic setting selection procedure that calculates the protection settings when there is a large amount of data to analyze. The proposed approach was validated by using a modified version of the IEEE 34-node test feeder with multiple distributed generators. The results showed the good performance of the methodology, since out of 4606 simulated cases, the calculated settings led to 97.86% of correct islanding detection and 0.98% of incorrect trips, considering the six passive protections operating simultaneously.Keywords
This publication has 17 references indexed in Scilit:
- Passive Method for Distributed-Generation Island Detection Based on Oscillation FrequencyIEEE Transactions on Power Delivery, 2015
- Development of frequency‐based anti‐islanding protection models for synchronous distributed generators suitable for real‐time simulationsIET Generation, Transmission & Distribution, 2015
- Review of the Impacts of Distributed Generation on Distribution Protection2015
- A smart device for islanding detection in distribution system operationElectric Power Systems Research, 2015
- A Practical Method for Nondetection Zone Estimation of Passive Anti-Islanding Schemes Applied to Synchronous Distributed GeneratorsIEEE Transactions on Power Delivery, 2014
- A review of islanding detection methods for microgridRenewable and Sustainable Energy Reviews, 2014
- A review of islanding detection techniques for renewable distributed generation systemsRenewable and Sustainable Energy Reviews, 2013
- Power imbalance application region method for distributed synchronous generator anti-islanding protection design and evaluationElectric Power Systems Research, 2011
- Review of islanding detection methods for distributed generation2008
- Efficient Coordination of ROCOF and Frequency Relays for Distributed Generation Protection by Using the Application RegionIEEE Transactions on Power Delivery, 2006