Sustainable Cooling in Warm Climates: Thermodynamic Optimisation of a LiBr–H2O Absorption Refrigeration System with Heat Recovery
Open Access
- 1 December 2025
- journal article
- research article
- Published by MDPI AG in Sustainability
- Vol. 17 (23) , 10765
Abstract
This study presents a comprehensive thermodynamic simulation and parametric analysis of a single-effect lithium bromide–water (LiBr–H2O) vapour absorption refrigeration system (VARS) to assess the influence of key operating parameters on its performance, which is primarily measured by the coefficient of performance. The thermodynamic properties of the LiBr–H2O solution are assessed using P-T-x diagrams to establish the operational limits of the cycle for given constraints, such as the absorber and the generator temperatures and the cycle’s operating pressures. The analysis includes the effects of generator temperature (), evaporator pressure (), and solution heat effectiveness () on the cycle performance. Additionally, exergy analyses of the cycle’s major components are performed. Simulation results demonstrate that is the most dominant parameter that increases the COP non-linearly from 0.35 at 85 °C to 0.73 at 110 °C (for = 0.5, = 40 °C), while the circulation ratio decreases sharply. Moreover, higher evaporator pressure positively influences the COP; for instance, increasing the evaporator pressure from 0.8 kPa to 1.2 kPa raised the COP from 0.71 to 0.76. This is directly correlated with the increased concentration difference between the strong and weak solutions. The heat recovery effectiveness proved vital for energy optimisation: increasing the recovery effectiveness from 0.5 to 0.9 improved the COP from approximately 0.72 to 0.82 at a fixed of 100 °C. Absorber temperatures limit the minimum operating temperatures of the generator for the vapour production of the refrigerant (water). Moreover, the higher condenser/absorber temperatures significantly deteriorate the performance of the cycle; for instance, raising the operating temperature of the condenser/absorber from 40 °C to 45 °C results in the COP value dropping by up to 35% at a generator operating temperature of nearly 100 °C. Among all cycle components, the generator exhibits the highest exergy loss, especially at lower generator temperatures. These findings provide essential optimisation strategies for designing and operating solar or waste heat-driven LiBr–H2O VARS units efficiently.
Keywords
Funding Information
- Deanship of Scientific Research (DSR) at King Abdulaziz University, Jeddah, Saudi Arabia (IPP: 354-135-2025)
This publication has 27 references indexed in Scilit:
- Energetic Analysis and Assessment of a Single-Effect LiBr–H2O Absorption Refrigeration System2024
- Modelling single-effect of Lithium Bromide-Water (LiBr–H2O) driven by an evacuated solar tube collector in Ma'an city (Jordan) case studyCase Studies in Thermal Engineering, 2022
- Solar-Driven Vapour Absorption (LiBr–H2O) Cooling Systems for Commercial Buildings: A Parametric Analysis2021
- Thermo-economic Comparison of Solar Heat Driven NH3–LiNO3 and NH3–H2O Absorption Refrigeration System2019
- Numerical Investigation on Solar Absorption Chiller with LiBr-H2O Operating Conditions and PerformancesEnergy Procedia, 2017
- Thermodynamic Evaluation of Generator Temperature in LiBr-Water Absorption System for Optimal PerformanceEnergy Procedia, 2017
- Exergetic and energetic comparison of LiCl-H 2 O and LiBr-H 2 O working pairs in a solar absorption cooling systemEnergy Conversion and Management, 2016
- Exergy analysis of a H 2 O–LiCl absorption refrigeration system with operating temperatures estimated through inverse analysisEnergy Conversion and Management, 2016
- Energy and exergy analysis of single effect and series flow double effect water–lithium bromide absorption refrigeration systemsInternational Journal of Refrigeration, 2009
- Thermodynamic analysis of absorption refrigeration cycles using the second law of thermodynamics methodInternational Journal of Refrigeration, 1995