Abstract
This paper discusses a simulation-based generator-level stability index and demonstrates the use of the index to quantify the impact of different load scenarios, transmission line reactances, and generator parameters on transient stability. A Basin Stability concept is used that is based on recent works in the physics community on complex systems and power systems, which estimates the regions of attraction through time-domain simulation. The quantitative results generated by Basin Stability can provide a general ranking metric to reflect which generator or a group of generators is likely to become unstable after disturbances. A detailed sub-transient model with sixth-order sub-transient generators, second-order exciters, and third-order power system stabilizers has been used for discussion. Additionally, a multi-node basin stability study on a 16-machine 68-bus system with the swing-equation model is also included to demonstrate the replicability. The state-of-the-art parallel computing techniques can significantly reduce the simulation time of the proposed method.

This publication has 37 references indexed in Scilit: