Frequency response analysis (FRA) is a technique for evaluating the mechanical integrity of power transformers. This paper proposes a methodology to locate inter-disc fault in a transformer winding through FRA measurements. A core-type three phase transformer is used for simulating faults on several locations along the interleaved winding, from top to bottom end. Correlation coefficient, vector fitting and Nyquist plot are employed to assist in the analysis. By drawing the transfer function of the winding response on Nyquist plot, key information is extracted and two equations are developed to locate the fault.Keywords
This publication has 6 references indexed in Scilit:
- Investigations on sensitivity of FRA method in diagnosis of interturn faults in transformer winding2011
- A New Method for Detection and Evaluation of Winding Mechanical Faults in Transformer through Transfer Function MeasurementsAdvances in Electrical and Computer Engineering, 2011
- Localization of winding radial deformation and determination of deformation extent using vector fitting‐based estimated transfer functionEuropean Transactions on Electrical Power, 2008
- Using Cross-Correlation Coefficients to Analyze Transformer Sweep Frequency Response Analysis (SFRA) Traces2007
- Investigations on sensitivity of FRA technique in diagnosis of transformer winding deformations2005
- Locating transformer faults through sensitivity analysis of high frequency modeling using transfer function approach2002