Abstract
This paper studies three different frequency controllers and their effects on the voltage disturbance ride-through capability of a VSC-HVDC supplied industrial system. The idea of implementing frequency controller is to improve the power quality of industrial plants by slightly decreasing the VSC output voltage frequency since industrial processes are more sensitive to voltage drops than frequency deviations. The first two controllers, frequency controllers I and II, are fixed frequency controllers and the third one, frequency controller III, is a PI frequency controller. In order to compare three different controllers, a system with a simplified VSC-HVDC and different load types is simulated in PSCAD/EMTDC. Simulation results show that with frequency controller III, the VSC-HVDC supplied industrial plant can avoid a voltage collapse by decreasing frequency during or after disturbances. Furthermore, with an increase of the converter current limit, the possibility of mitigating voltage dips increases. For frequency controllers I and II, the extent of the disturbance ride-through capability depends on the current limit of the VSC-HVDC. A higher current limit results in a higher ride-through capability. The effect of the dc capacitor on improving the system voltage disturbance tolerance is also investigated during and after disturbances when the VSC-HVDC uses frequency controller I. The system voltage disturbance ride-through capability increases with an increase of the dc capacitance or the current limit.Keywords
This publication has 16 references indexed in Scilit:
- A New Control Strategy of a VSC–HVDC System for High-Quality Supply of Industrial PlantsIEEE Transactions on Power Delivery, 2007
- Latest control and protection innovations applied to the Basslink HVDC interconnector2006
- Analysis of the control algorithms of voltage-source converter HVDC2005
- A voltage and frequency droop control method for parallel inverters2005
- Stability of voltage and frequency control in distributed generation based on parallel-connected converters feeding constant power loads2005
- Eagle Pass back-to-back tie: a dual purpose application of voltage source converter technology2001
- Voltage sags: their impact on the utility and industrial customersIEEE Transactions on Industry Applications, 1998
- Operating experience of Hokkaido-Honshu high voltage direct current linkIEEE Transactions on Power Delivery, 1997
- Auxiliary power controls on the Nelson River HVDC schemeIEEE Transactions on Power Systems, 1992
- Adaptation of the control equipment to permit 3-terminal operation of the HVDC link between Sardinia, Corsica and mainland ItalyIEEE Transactions on Power Delivery, 1989