A study on heat transfer load in large space buildings with stratified air-conditioning systems based on building energy modeling: Model validation and load analysis
Authors:
Open Access
- 27 July 2021
- journal article
- research article
- Published by SAGE Publications in Science Progress
- Vol. 104 (3)
Abstract
The characteristics of heat transfer load from the non-air-conditioned (NAC) area can help to understand the complex airflow movement and thermal physical mechanisms inside large space buildings. Based on building energy modeling, the indoor thermal environment and building energy consumption of a plant for computerized numerical control (CNC) machine tools are studied. Considering the form of the stratified air-conditioning system and the phenomenon of heat retention near the roof in the plant, the double zone and triple zone models are established. The vertical air temperature, the parameters of the terminal of the air-conditioning system and the heat/cool source system of the plant in summer and winter were measured on site, which verifies the accuracy of the established model. Based on the validated model, the proportion of heat transfer load from the NAC area is calculated, at the range of about 60%–85%. The positive influence of the roof heat transfer coefficient on the sensible heat load in the NAC area is revealed. The recommended value of the non-dimensional zone-mixing flow rate between the air-conditioned (AC) and NAC areas is given, with 30% (in summer). The results of this work can help understand the composition of the stratified air-conditioning load in large spaces and optimize the design of air distribution.Keywords
Funding Information
- Machinery Industry Innovation Platform Construction Project of China (2019SA-10-07)
- National Natural Science Foundation of China (51708054)
This publication has 21 references indexed in Scilit:
- On-site measured indoor thermal environment in large spaces of airports during winterBuilding and Environment, 2020
- Evaluation of thermal environment by coupling CFD analysis and wireless-sensor measurements of a full-scale room with cooling systemSustainable Cities and Society, 2019
- Thermal buoyancy driven flows inside the industrial buildings primarily ventilated by the mechanical fans: Local facilitation and infiltrationEnergy and Buildings, 2018
- Analysis of the influence of the return position in the vertical temperature gradient in displacement ventilation systems for large hallsEnergy and Buildings, 2017
- Study on present situation and optimization strategy of infiltration air in a train station in winterProcedia Engineering, 2017
- A review of the advance of HVAC technologies as witnessed in ENB publications in the period from 1987 to 2014Energy and Buildings, 2016
- Energy Research in Airports: A ReviewEnergies, 2016
- Performance analysis of the air-conditioning system in Xi’an Xianyang International AirportEnergy and Buildings, 2013
- CFD study of the thermal environment in an air-conditioned train station buildingBuilding and Environment, 2009
- Measurement of thermal stratification in large single-cell buildingsEnergy and Buildings, 1996