Influence of the Cable Accessories Installing Method on the Partial Discharge Activity in Medium Voltage Cables
Open Access
Abstract
This article proposes a method to modify the construction of a medium voltage (MV) heat shrinkable cable termination in cases of atypical damage to the shields of cross-linked polyethylene (XLPE) insulated cables. The proposed solutions include a modified method of assembling electric field control coating. An attempt was made to check the effect of such damage to the shields of MV cables with XLPE insulation on the level of occurrence of partial discharges within the cable termination. The investigations included testing the XRUHAKXS 1 × 240/25 cable type using the electric method (ME) and high frequency (HF) method with sinusoidal AC test voltage. As a result of the measurements, the values of total charges in the period and phase-resolved partial discharge (PRPD) patterns were obtained. The presented experimental results show the influence of the damage of the semiconducting coating surface on the occurrence of a defect in the cable termination without a modified method of control mantissa pinning. We suggest new methods of assembling MV cable accessories in the case of the presented coating damage in MV cable insulation.Keywords
This publication has 33 references indexed in Scilit:
- Underground MV power cable joints: A nonlinear thermal circuit model and its experimental validationElectric Power Systems Research, 2017
- High noise tolerance feature extraction for partial discharge classification in XLPE cable jointsIEEE Transactions on Dielectrics and Electrical Insulation, 2017
- Classification of Partial Discharge Measured under Different Levels of Noise ContaminationPLOS ONE, 2017
- Partial discharge detection in medium voltage and high voltage cables: maximum distance for detection, length of cable, and some answersIEEE Electrical Insulation Magazine, 2016
- Application of HFCT and UHF Sensors in On-Line Partial Discharge Measurements for Insulation Diagnosis of High Voltage EquipmentSensors, 2015
- Research on partial discharge mechanism and characteristics for 10kV cable joint with air gap defect2014
- The partial discharge characteristic of typical XLPE cable insulation defects under damped oscillating voltage2014
- An improved optimal design scheme for high voltage cable accessoriesIEEE Transactions on Dielectrics and Electrical Insulation, 2014
- Partial Discharge Pattern Recognition by Neuro-Fuzzy Networks in Heat-Shrinkable Joints and Terminations of XLPE Insulated Distribution CablesIEEE Transactions on Power Delivery, 2006
- PD knowledge rules for insulation condition assessment of distribution power cablesIEEE Transactions on Dielectrics and Electrical Insulation, 2005