PG and E'S Cool Fog Tests on Artificially Contaminated Suspension Insulators
Authors:
- 1 September 1974
- journal article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Power Apparatus and Systems
- Vol. PAS-93 (5) , 1318-1327
Abstract
The results of artificial contamination tests on a variety of porcelain and glass suspension insulators are presented together with a discussion of the contamination and fogging procedures. The results are presented in an analytical form that can be related to a theoretical flashover criterion. Semiconductive glazed insulators were tested and compared to normally glazed insulators of the same type.Keywords
This publication has 9 references indexed in Scilit:
- Development of New Semiconductive Glaze InsulatorsIEEE Transactions on Power Apparatus and Systems, 1974
- A Study on Dynamic Voltage Distribution on Contaminated Insulator SurfaceIEEE Transactions on Power Apparatus and Systems, 1973
- Contamination Flashover, Part I: Theoretical AspectsIEEE Transactions on Power Apparatus and Systems, 1972
- Resistance Graded Insulators - The Ultimate Solution to the Contamination Problem?IEEE Transactions on Power Apparatus and Systems, 1972
- Anti-Pollution Design Criteria for Line and Station InsulatorsIEEE Transactions on Power Apparatus and Systems, 1972
- A Study of the Performance of Contaminated Insulators Under Various Test ConditionsIEEE Transactions on Power Apparatus and Systems, 1971
- A Survey of The Problem of Insulator Contamination in The United States and Canada-Part IIEEE Transactions on Power Apparatus and Systems, 1971
- Effect of pollution on high-voltage outdoor insulatorsProceedings of the Institution of Electrical Engineers, 1971
- Application of dimensional analysis to flashover characteristics of polluted insulatorsProceedings of the Institution of Electrical Engineers, 1970