Experimental Investigation on Outdoor Insulation for DC Transmission Line at High Altitudes
Authors:
- 8 December 2009
- journal article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Power Delivery
- Vol. 25 (1) , 351-357
Abstract
This paper presents the results of a study on the contamination characteristics of porcelain, glass and composite insulators in natural high altitude areas (1970 m). The test used the solid layer method, in which a contaminant solution consisting of sodium chloride, kaolin powder and water was used to coat the insulator surfaces. The insulators were wetted by steam fog in fog chamber. The 50% withstand voltage (U 50%) was determined by the up-and-down method. Experimental results indicate that insulator profiles have a significant effect on the flashover voltages. The flashover voltages for bell-type porcelain insulator are higher than tri-shed porcelain insulator. The glass insulator with bigger spacing has a higher flashover voltage than that with smaller spacing. The flashover characteristics of composite insulators can be greatly improved for about 20% by optimizing the shed parameters. In addition, the suspension patterns (I-, V- and Y-string) also have a significant influence on the porcelain insulator flashover voltages. The Y-string configuration appears to lead to much lower flashover voltages than I- and V-string insulators. The flashover voltages for V-string insulators are influenced by the angle between two insulator strings. The flashover voltage for V-strings of 120 ° is highest, which is higher than that of I-string for 7.5%.Keywords
This publication has 12 references indexed in Scilit:
- Fundamental and low frequency harmonic components of leakage current as a diagnostic tool to study aging of RTV and HTV silicone rubber in salt-fogIEEE Transactions on Dielectrics and Electrical Insulation, 2003
- DC flashover characteristics of the contaminated insulators under low atmospheric pressure2003
- Discharge performance of different models at low pressure air2002
- Outdoor HV composite polymeric insulatorsIEEE Transactions on Dielectrics and Electrical Insulation, 1999
- Effect of climatic conditions on contamination flashover voltage of insulatorsIEEE Transactions on Dielectrics and Electrical Insulation, 1997
- Effect of insulator profiles on DC flashover voltage under polluted conditions. A study using a dynamic arc modelIEEE Transactions on Dielectrics and Electrical Insulation, 1994
- Polymer insulator profiles evaluated in a fog chamberIEEE Transactions on Power Delivery, 1990
- New DC insulator design for use in the desert environmentIEEE Transactions on Electrical Insulation, 1990
- A study on the profile of HVDC insulators-DC flashover performanceIEEE Transactions on Electrical Insulation, 1989
- EPRI-HVDC Insulator, Studies: Part II Laboratory Simulation StudiesIEEE Transactions on Power Apparatus and Systems, 1981