Cooling Mechanisms of Switching Arcs Under Transverse Magnetic Fields in Comparison With Arcs Without Magnetic Blast
- 17 January 2018
- journal article
- research article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Plasma Science
- Vol. 46 (2) , 444-450
Abstract
The importance of low-voltage devices to interrupt dc currents under load and fault conditions has been considerably growing recently. From experimental work, it is known that arcs in strong transverse magnetic fields (e.g., flux density 1 T) can generate arc voltages considerably higher than those generated without field. In a recent study, it was shown by the author in 2-D simulations that in arrangements where the arc is magnetically squeezed against a chamber wall, the dominant mechanism of power removal is convection propelled by the JxB force (``electromagnetic pump''). Immediately in front of the wall the convective heat flux is converted to heat conduction toward the cold wall. This subsequent work is concentrated on the mechanism of free-moving arcs in transverse magnetic fields. Here, a similar effect of voltage increase has been known, but the cold wall as final target of power transport is missing. For differentiation, the cooling mechanism of arcs in chambers without magnetic blast field is also studied. While the temperature profiles and consequently the arc field strength for still arcs in chambers are dominated either by heat conduction or by radiation, depending on the current, free-moving arcs in cross fields are mainly cooled by the convective JxB pump. Heat conduction is negligible. Power is consumed by the heating of the plasma gas masses, which can be visualized by an equivalent flux. Values of the arc field strength, i.e., voltage per arc length, are also presented for dc currents between 4 and 1000 A. They increase in the sequence ``chamber without field'', ``free arc with cross field'', and ``chamber with cross field''. In comparison with air, hydrogen yields clearly higher voltages.Keywords
This publication has 7 references indexed in Scilit:
- Simulation of Switching Arcs Under Transverse Magnetic Fields for DC InterruptionIEEE Transactions on Plasma Science, 2016
- Fundamental characteristics of arc extinction by magnetic blow-out at DC voltages (<500V)2014
- DC-arc blowing under pulsed magnetic field2012
- Breaking performance of a circuit breaker influenced by a permanent magnetic field at DC voltages up to 450 V2012
- Low-Voltage Arc Simulation with Out-Gassing Polymers2011
- Magnetic Blowing of Break Arcs up to 360 VDC2010
- Grundlagen der Schaltgerätetechnik1974