Liquid-Immersed Distribution Transformers’ Thermal Analysis With Consideration of Unbalanced Load Current Effect
- 14 July 2023
- journal article
- research article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Dielectrics and Electrical Insulation
- Vol. 31 (1) , 339-349
Abstract
Distribution transformers (DTs) are the most costly and crucial power grid equipment, and accurate investigation of their thermal status can prevent their failure, since insulation condition directly correlates with hotspot temperature (HST). In this article, an accurate and nonuniform magnetic–thermal analysis of DT is proposed for precise HST prediction. In the magnetic analysis, the DT is modeled as a 2-D axial symmetry, and the losses calculation of the windings has been fulfilled as a nonuniform. In the thermal analysis, the DT is modeled as 3-D and nonuniform, and the conservator and core stacking, which has a considerable effect on the HST, are precisely modeled. By taking advantage of optical fiber sensors (OFSs) in the understudied 500-kVA DT, the accuracy of the proposed nonuniform 3-D computational fluid dynamic (CFD)-based modeling during the temperature rise test (TRT) is validated. The empirical evaluation results depict that the presented nonuniform CFD-based thermal analysis for HST prediction is very precise, and there is an appropriate vicinity to the experimental values. The error percentage of the proposed 3-D CFD-based thermal analysis is 0.11% (0.1 °C) compared with the OFSs measurements, which demonstrates the precision and effectiveness of the presented modeling. Also, the verification of the results of nonuniform 3-D CFD-based thermal analysis in top-oil temperature (TOT) and bottom-oil temperature (BOT) during the experimental TRT is fulfilled via thermography. According to the attained evaluated results, temperatures of 3-D CFD-based thermal analysis and thermography in the noted two points are in good accordance with each other. In short, the error percentage is less than 0.65%, which indicates the correctness and proper performance of the proposed 3-D CFD-based modeling. Finally, the proposed nonuniform 3-D model was subjected to the unbalanced load currents of 0.95, 1.05, 1.1, 1.15, and 1.2 of rated current, which increased the HST by −1.6 °C, 1.3 °C, 2.8 °C, 4.3 °C, and 6.0 °C, respectively, over the original model without unbalanced load currents.Keywords
Funding Information
- Center for Research on Microgrids (CROM), Villum Fonden, under the Villum Investigator (25920)
This publication has 32 references indexed in Scilit:
- Magnetic-thermal analysis of distribution transformer: Validation via optical fiber sensors and thermographyInternational Journal of Electrical Power & Energy Systems, 2023
- Precise thermo-fluid dynamics analysis of corrugated wall distribution transformer cooled with mineral oil-based nanofluids: Experimental verificationApplied Thermal Engineering, 2022
- Comprehensive comparative analysis of Metal-Oxide nanoadditives impacts on Oil-Filled Finemet and Vitroperm alloy core transformers HST concerning nanofluid thermophysical properties accurate estimationEnergy Conversion and Management, 2022
- Investigation of Mineral Oil-Based Nanofluids Effect on Oil Temperature Reduction and Loading Capacity Increment of Distribution TransformersEnergy Reports, 2021
- Thermal behavior investigation of installation orientation and color effect on distribution transformers using E-TRM method and its effect on loadingEngineering Science and Technology, an International Journal, 2021
- Indoor distribution transformers oil temperature prediction using new electro‐thermal resistance model and normal cyclic overloading strategy: an experimental case studyIET Generation, Transmission & Distribution, 2020
- A Method for Hot Spot Temperature Prediction of a 10 kV Oil-Immersed TransformerIEEE Access, 2019
- Thermal management of a distribution transformer: An optimization study of the cooling system using CFD and response surface methodologyInternational Journal of Electrical Power & Energy Systems, 2019
- Assessment of a hydraulic network model for zig–zag cooled power transformer windingsApplied Thermal Engineering, 2015
- Thermal modeling of power transformers using evolving fuzzy systemsEngineering Applications of Artificial Intelligence, 2012