Field electron emission current in vacuum interrupters after large inrush current
Authors:
- 1 September 2012
- conference paper
- Published by Institute of Electrical and Electronics Engineers (IEEE)
- p. 157-160
Abstract
Field electron emission (FEE) current in the open(ing) gap of nine different designs of 36 kV vacuum interrupters under standard recovery voltage conditions was measured during full-power back-to-back capacitive switching. During closing operation, 20 kA inrush current (@ 4250 Hz) was applied. The measurement system is described, able to measure FEE current with a threshold of 30 μA but that also has to withstand a full capacitor bank discharge current of up to 40 kA after re-strike. It was concluded that in spite of the wide variety of measured FEE current magnitude (up to several mA) there is no direct relationship between magnitude of FEE current and probability of breakdown. Longer arc duration of the normal load current reduces the FEE current level after load current interruption.Keywords
This publication has 7 references indexed in Scilit:
- Field emission currents in vacuum breakers after capacitive switchingIEEE Transactions on Dielectrics and Electrical Insulation, 2011
- Measurement of field emission current during switching of capacitive current in vacuum2010
- Switching of capacitive current with vacuum interrupters2010
- Late breakdown phenomena in vacuum interrupters2008
- Switching of capacitive currents and the correlation of restrike and pre-ignition behaviorIEEE Transactions on Dielectrics and Electrical Insulation, 2006
- An investigation into major factors in shunt capacitor switching performances by vacuum circuit breakers with copper-chromium contactsIEEE Transactions on Power Delivery, 1993
- Vacuum Electrical Breakdown between Plane-Parallel Copper ElectrodesJournal of Applied Physics, 1966