Thermal and luminic comfort assessment in university classrooms in Tijuana, Baja California. Case of study FCITEC, Valle de las Palmas
Authors:
- María Teresa De la Cruz ChaidezMCMaría Teresa De la Cruz Chaidez
- José Francisco Armendáriz LópezJLJosé Francisco Armendáriz López
- Francisco José Martín del Campo SarayFSFrancisco José Martín del Campo Saray
- Miguel Isaac Sahagún ValenzuelaMVMiguel Isaac Sahagún Valenzuela
- María Cristina Castañón BautistaMBMaría Cristina Castañón Bautista
Open Access
- 6 October 2022
- journal article
- research article
- Published by Facultad de Ciencias de la Ingenieria y Tecnologia de la UABC in REVISTA DE CIENCIAS TECNOLÓGICAS
- Vol. 5 (4) , 419-452
Abstract
About 2022, studies on environmental conditions inside classrooms have increased because they are related to well-being, performance, and student productivity in terms of concentration, attention, and learning during school hours. Assessing the conditions of the educational space once inhabited can be fundamental to identifying environmental adjustments that could improve achievement in learning through design strategies in school facilities in the locality. The evaluation of the thermal and luminic conditions of three classrooms designed to function with natural ventilation, in two buildings of the Universidad Autónoma of Baja California, in Tijuana, Mexico, during the cold-warm transition period is presented. Physical measurements of environmental indicators were made, including temperature, relative humidity, and daylight. A total of 181 students completed the environmental survey questionnaires. This study aimed to evaluate the interior environmental space conditions and determine the influence on occupants' comfort. Results showed that more than 50% of the students were in a thermal discomfort situation when the temperature was out of the range of 19.7°C -27.7° C, consistent with the application of the ASHRAE Adaptative Comfort Zones. Daylight values were below the minimum required of 300 Lux for educational classroom specificity in [1, 2] of the three classrooms. Building's orientations, West and South registered illuminance values that could produce glare and increase thermal discomfort due to high solar radiation. The results confirmed the close relationship between environmental conditions and students' comfort in classrooms.Keywords
This publication has 30 references indexed in Scilit:
- Assessment of natural lighting performance and visual comfort of educational architecture in Southern Europe: The case of typical educational school premises in CyprusEnergy and Buildings, 2017
- Visual comfort assessment of daylit and sunlit areas: A longitudinal field survey in classrooms in Kashan, IranEnergy and Buildings, 2016
- Retrofit Strategies for the Improvement of Visual Comfort and Energy Performance of Classrooms with Large Windows Exposed to EastEnergy Procedia, 2015
- A thermal comfort field study of naturally ventilated classrooms in Kharagpur, IndiaBuilding and Environment, 2015
- The impact of classroom design on pupils' learning: Final results of a holistic, multi-level analysisBuilding and Environment, 2015
- Evaluation of thermal comfort in university classrooms through objective approach and subjective preference analysisApplied Ergonomics, 2015
- Occupants’ adaptive responses and perception of thermal environment in naturally conditioned university classroomsApplied Energy, 2010
- Thermal comfort in Italian classrooms under free running conditions during mid seasons: Assessment through objective and subjective approachesBuilding and Environment, 2009
- Field experiments on thermal comfort in campus classrooms in TaiwanEnergy and Buildings, 2006
- Acoustic, thermal and luminous comfort in classroomsBuilding and Environment, 2004