Study on the stability mechanism of the sending‐side three‐machine‐group system after multiple HVDC commutation failure
Authors:
Open Access
- 1 January 2017
- journal article
- research article
- Published by Institution of Engineering and Technology (IET) in The Journal of Engineering
- Vol. 2017 (13) , 1140-1145
Abstract
Under the new situation of the ‘strong DC and weak AC’, the interaction between the sending‐side and the receiving‐side AC systems interconnected by HVDC links is becoming significant, and the contingencies can be transmitted via the DC power response. In this study, the rotor motion equation of the three‐machine system is derived. The decoupling of the two stability modes is realised according to their inherent periodic relationship, and the stability mechanism of the sending‐side three‐machine system after multiple HVDC commutation failure is analysed applying the equal‐area criterion. The impact of the influential factors on the stability of the sending‐side system is then analysed. The results are verified by the three‐machine equivalent case system and the ‘North China‐Central China‐East China’ practical system.Keywords
This publication has 3 references indexed in Scilit:
- Analysis of the sending-side system instability caused by multiple HVDC commutation failureCSEE Journal of Power and Energy Systems, 2015
- Research on dynamic characteristics and countermeasures of AC-DC hybrid power system with large scale HVDC transmission2014