Abstract
Shell-and-tube heat exchanger performance is governed by competing thermal and hydraulic objectives that single-variable optimisation cannot resolve simultaneously. This study introduces a unified surrogate-assisted framework in which baffle inclination angle θ ∈ [-25◦,25◦] and perforation diameter d ∈[2,5] mm are treated as continuous co-design variables. A twelve-member ANN ensemble trained on 35 CFD-generated samples serves as the frozen evaluation oracle for four independent optimisation paradigms: NSGA-II, Bayesian optimisation, particle swarm optimisation, and deep reinforcement learning. Saturation diagnostics confirmed surrogate fidelity prior to every run. Perforation diameter emerged as the dominant hydraulic lever, with large perforations triggering a shift from recirculation-dominated cross-flow to jet-assisted wake suppression that reduces friction substantially without proportional thermal penalty. DRL-PPO located the globally superior con figuration (θ = 20.88◦, d = 4.46 mm), achieving a CFD-verified thermo hydraulic ratio of j/f = 0.01264: an 18.6% gain over the conventional perpendicular unperforated baseline, a 20.0% improvement over the PEC optimal solid inclined reference, and a 35.1% friction factor reduction relative to the same inclined solid reference. All surrogate prediction errors remained below 2.8% at verified optima, establishing physical credibility of the reported improvements.

This publication has 44 references indexed in Scilit: