A Current-Comparator-Based Wattmeter for High Voltage Power Measurements at Very Low Power Factors
Author:
- 1 January 1987
- journal article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Power Delivery
- Vol. 2 (4) , 1018-1024
Abstract
A current-comparator technique for obtaining a wattmeter for accurate high voltage power measurements at very low power factors is described. The quadrature component of the load cturrent is automatically balanced in the current comparator against a quadrature current obtained from a slave supply, thereby reducing the stringent high accuracy requirement of the wattmeter when used for measuring power at very low power factors. The current-comparator-based wattmeter has an estimated accuracy with respect to its readings of better than 3 percent at 0.001 power Factor, 1 percent at 0.005 power factor, and 0.5 percent at 0.01 power factor and higher. It features an internal high-voltage active-divider and displays to indicate source voltage, current, power factor, and reactance of the load, in addition to the power.Keywords
This publication has 11 references indexed in Scilit:
- An active high-voltage divider and phase shifterIEEE Transactions on Instrumentation and Measurement, 1987
- The Application of the Current Comparator in Instrumentation for High Voltage Power Measurements at Very Low Power FactorsIEEE Transactions on Power Delivery, 1986
- A Wideband Sampling Wattmeter1IEEE Transactions on Power Apparatus and Systems, 1984
- A Comparison of Instrumentation for Measuring the Losses of Large Power TransformersIEEE Transactions on Power Apparatus and Systems, 1983
- A Current-Comparator-Based System for Calibrating Active/Reactive Power and Energy MetersIEEE Transactions on Instrumentation and Measurement, 1983
- The Development of an Automatic-Reversing Differential Thermal WattmeterIEEE Transactions on Instrumentation and Measurement, 1980
- Measurement of short circuit load losses in large three phase power transformers using an alternating current comparator bridgeIEEE Transactions on Power Apparatus and Systems, 1975
- Measurement of Shunt Reactor Loss at High Voltage with an Alternating Current Comparator BridgeIEEE Transactions on Power Apparatus and Systems, 1973
- A Transformer-Ratio-Arm Bridge for Measuring Large Capacitors Above 100 VoltsIEEE Transactions on Power Apparatus and Systems, 1968
- A Self-Balancing Current ComparatorIEEE Transactions on Instrumentation and Measurement, 1966