Study on the Control Strategy for Parallel Operation of Inverters Based on Adaptive Droop Method
- 1 May 2006
- conference paper
- Published by Institute of Electrical and Electronics Engineers (IEEE)
- p. 1-5
Abstract
This paper studies droop method based wireless parallel operation of inverters. With conventional droop method, the voltage deviation is usually quite severe to achieve good power sharing among the inverters connected in parallel. To overcome this problem, an adaptive droop method is developed by which the trade-off between voltage regulation and power sharing is relieved significantly. In addition, the second order filter rather than the first order filter that is adopted to obtain the average power drawn from each module improves the transient response. Experiment has been carried out on the system with two inverters in parallel. The results have validated the strategy developedKeywords
This publication has 10 references indexed in Scilit:
- A Wireless Controller to Enhance Dynamic Performance of Parallel Inverters in Distributed Generation SystemsIEEE Transactions on Power Electronics, 2004
- A high-performance DSP-controller for parallel operation of online UPS systems2004
- Novel architectures and control for distributed UPS systems2002
- Control of distributed UPS systems2002
- Parallel operation of single phase inverter modules with no control interconnections2002
- A novel droop method for converter parallel operationIEEE Transactions on Power Electronics, 2002
- Control of parallel inverters in distributed AC power systems with consideration of line impedance effectIEEE Transactions on Industry Applications, 2000
- Parallel operation control technique of voltage source inverters in UPS1999
- Analysis and design of a multiple feedback loop control strategy for single-phase voltage-source UPS invertersIEEE Transactions on Power Electronics, 1996
- Parallel operation of voltage source invertersIEEE Transactions on Industry Applications, 1988