Influence of lightning flashover criterion on the calculated lightning withstand level of ±800 kV UHVDC transmission lines at high altitude
Authors:
- 12 February 2015
- journal article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Dielectrics and Electrical Insulation
- Vol. 22 (1) , 185-191
Abstract
The operation experiences of power transmission lines show the lightning outage is still the main part of the total outage rate. So it is very important to calculate the lightning overvoltage across the insulators precisely and evaluate the lightning outage of the transmission lines correctly. Lightning flashover criterion of the insulator/gap is one of the most important factors that influence the precise calculation results of the lightning withstand level of transmission lines. In China, several ±800 kV ultra high voltage direct current (UHVDC) power transmission projects have been set up in recent years, and the altitude of the regions that the transmission lines across ranges from 0-3650 m. The paper mainly analyzed the influence of the modelling methods of insulator/gap on the lightning withstand level of ±800 kV UHVDC transmission lines by PSCAD/EMTDC program. The compared lightning flashover criteria of insulator/gap include the leader propagation model recommended by CIGRE, the volt/time curve recommended by IEEE and an improved leader propagation model, which is proposed based on the lightning flashover experiments of the ±800 kV UHVDC line insulators carried out at an altitude of 2100 m. Meanwhile, the influences of lightning current waveform and insulator structure were also considered and compared. The simulation results show that the calculated back-flashover lightning withstand level is much lower when using the improved leader propagation than that using other flashover criterions in the paper, it is lower under the 2.6/50 μs double exponential lightning current than that under the 2.0/50 μs Heidler function lightning current, and it is higher when using V-string than that using I-string insulator. Besides, the influences of the lightning current waveform and the insulator structure on the calculation of shielding failure lightning withstand level are little, but the flashover criterion has obvious influences on the shielding failure lightning withstand level.Keywords
This publication has 10 references indexed in Scilit:
- Influence of Modeling Methods on the Calculated Lightning Surge Overvoltages at a UHVDC Converter Station Due to BackflashoverIEEE Transactions on Power Delivery, 2012
- Lightning overvoltage due to first strokes considering a realistic current representationIEEE Transactions on Electromagnetic Compatibility, 2010
- Evaluation of Improved Lightning Stroke Current Waveform Using Advanced Statistical MethodIEEE Transactions on Power Delivery, 2009
- Observational Results of Lightning Current on Transmission TowersIEEE Transactions on Power Delivery, 2006
- A Method of a Lightning Surge Analysis Recommended in Japan Using EMTPIEEE Transactions on Power Delivery, 2005
- Parameters of lightning strokes: a reviewIEEE Transactions on Power Delivery, 2005
- Calculation of lightning current parametersIEEE Transactions on Power Delivery, 1999
- Modelling of a transmission tower for lightning-surge analysisIEE Proceedings - Generation, Transmission and Distribution, 1996
- Experimental evaluation of a UHV tower model for lightning surge analysisIEEE Transactions on Power Delivery, 1995
- Critical switching impulse strength of long air gaps: modelling of air density effectsIEEE Transactions on Power Delivery, 1992