Estimation of damping resistor in mechanically switched capacitor with damping network at different tuning frequencies during switching
Authors:
- 1 October 2015
- conference paper
- Published by Institute of Electrical and Electronics Engineers (IEEE)
- p. 839-843
Abstract
Mechanically switched capacitor with damping network (MSCDN) is a low cost economical device used in power systems to serve the dual purpose of supplying reactive power at the fundamental frequency as well as to eliminate the unwanted harmonics when tuned at the desired harmonic frequency. However, during switching in a high voltage A.C grid, various elements of an MSCDN plant are subjected to transient electrical stresses which may be vulnerable for the insulation. Proper designing of the damping network is therefore key to mitigate the switching transients. Hence, in this contribution transient analysis is performed on an exemplary MSCDN model for various values of damping resistor at different tuning frequencies. Finally, an optimum range of damping resistor values have been proposed for designing a MSCDN plant tuned to different harmonic frequencies.Keywords
This publication has 4 references indexed in Scilit:
- Basic design considerations for a mechanically switched capacitor with damping network (MSCDN) within a high-voltage-grid2013
- Novel design methodology for C-type harmonic filter banks applied in HV and EHV networks2012
- Mechanically Switched Capacitor with Damping Network (MSCDN) - Engineering aspects of application, design and protection2010
- Impact of reactive power compensation equipment on the harmonic impedance of high voltage networks2004