Abstract
The Active Front End (AFE) is interconnected to the grid with an LCL filter to reduce the switching harmonics. Possible resonances induced by the LCL filter can be damped using Active Damping (AD). In AFE applications, the current sensor can be placed on either the grid-side or the converter-side, resulting in different frequency responses. This paper presents a novel active damping approach that is universally applicable to all active front end converters regardless of whether the current sensor is placed on the grid side or the converter side. At the heart of the proposed approach is a practically implementable fourth-order filter that dampens the resonance whilst being capable of mitigating the challenges associated with both grid current feedback and converter current feedback. These include amplifications associated with derivatives in active damping term with grid current feedback and high susceptibility to instability with converter current feedback due to digital delay. The proposed active damping is thoroughly investigated in terms of practical implementation issues such as different LCL filter parameters, different sampling methods, grid impedance, and digital delay. The approach is experimentally validated on motor drives consisting of 2 two-level three-phase converters interfaced with a dSPACE rapid control prototyping system across a wide range of resonant frequencies and PWM sampling methods. Stability analysis is performed on both current control methods to validate that active damping assures stable operation for a wide range of resonant frequencies and grid impedance.Keywords
Funding Information
- Australian Research Council (FT150100042, LP170100902)
This publication has 28 references indexed in Scilit:
- Harmonic Analysis of Grid Connected Power Electronic Systems in Low Voltage Distribution NetworksIEEE Journal of Emerging and Selected Topics in Power Electronics, 2015
- Optimal Design of High-Order Passive-Damped Filters for Grid-Connected ApplicationsIEEE Transactions on Power Electronics, 2015
- Grid-Current-Feedback Active Damping for LCL Resonance in Grid-Connected Voltage-Source ConvertersIEEE Transactions on Power Electronics, 2015
- Automatic Tuning of Cascaded Controllers for Power Converters Using Eigenvalue Parametric SensitivitiesIEEE Transactions on Industry Applications, 2014
- New Hybrid Damping Strategy for Grid-Connected Photovoltaic Inverter With LCL FilterIEEE Transactions on Applied Superconductivity, 2014
- Influence of Delay on System Stability and Delay Optimization of Grid-Connected Inverters With LCL FilterIEEE Transactions on Industrial Informatics, 2014
- Active Damping-Based Control for Grid-Connected $LCL$ -Filtered Inverter With Injected Grid Current Feedback OnlyIEEE Transactions on Industrial Electronics, 2013
- $LCL$ Filter Design and Performance Analysis for Grid-Interconnected SystemsIEEE Transactions on Industry Applications, 2013
- Regions of Active Damping Control for LCL FiltersIEEE Transactions on Industry Applications, 2013
- Motor drive technology - history and visions for the future2004