Abstract
This paper describes the investigation of the insulation condition of a number of power and distribution type transformers of different manufacturing dates and with different operating histories. Return voltage measurements were conducted for these transformers. Effects of moisture and aging on the oil-paper insulation of these transformers were investigated and results are presented in this paper. Moisture in oil samples at known temperature was measured for these transformers. Previously accelerated aging experiments were performed on paper wrapped insulated conductors in different environments over a temperature range of 115 to 145/spl deg/C. Results from the measurements on transformers are compared with those of the accelerated aged samples and are described in this paper.Keywords
This publication has 9 references indexed in Scilit:
- Degradation of electrical insulating paper monitored using high performance liquid chromatography2003
- Moisture equilibrium in transformer paper-oil systemsIEEE Electrical Insulation Magazine, 1999
- Investigating the effects of oxidation and thermal degradation on electrical and chemical properties of power transformers insulationIEEE Transactions on Power Delivery, 1999
- Investigations into effective methods for assessing the condition of insulation in aged power transformersIEEE Transactions on Power Delivery, 1998
- Electrical and chemical diagnostics of transformers insulation. B. Accelerated aged insulation samplesIEEE Transactions on Power Delivery, 1997
- Electrical and chemical diagnostics of transformers insulation. A. Aged transformer samplesIEEE Transactions on Power Delivery, 1997
- A study of degradation of cellulosic insulation materials in a power transformer. Part 2: tensile strength of cellulose insulation paperPolymer Degradation and Stability, 1995
- A study of degradation of cellulosic insulation materials in a power transformer, part 1. Molecular weight study of cellulose insulation paperPolymer Degradation and Stability, 1995
- A review of paper aging in power transformersIEE Proceedings C Generation, Transmission and Distribution, 1985