Study on the Bending Stiffness of Joints Connecting Porcelain Bushings and Flanges in Ultra-High Voltage Electrical Equipment
Open Access
- 9 June 2022
- journal article
- research article
- Published by MDPI AG in Applied Sciences
- Vol. 12 (12) , 5899
Abstract
In this study, the equivalent bending stiffness of cement-bonded joints connecting the porcelain bushing and flange in ultra-high voltage (UHV) electrical equipment was investigated. A mechanical bending model of the joint was developed based on its structural features, and a new equation for the equivalent bending stiffness of the joint was proposed. Based on experimental data for nine UHV porcelain bushings, a dimensionless elasticity coefficient for the equivalent bending stiffness equation was determined. Finally, considering two 1000 kV arresters as examples, the bending stiffness was calculated using the equation proposed in this paper and that which is used in China’s seismic code. A comparison of the results shows that the equation proposed in this study is in better agreement with the experimental data. Compared with the code equation, the equation in this paper adopts the expression for the dimensionless coefficient, which can more reasonably reveal the bending mechanism of the joint.Keywords
Funding Information
- Hubei Electric Power Research Institute (SGRI-WD-71-15-101)
This publication has 10 references indexed in Scilit:
- Study on Seismic Performance of Porcelain Pillar Electrical Equipment Based on Nonlinear Dynamic TheoryAdvances in Civil Engineering, 2021
- On the Nonlinear Seismic Responses of Shock Absorber-Equipped Porcelain Electrical ComponentsMathematical Problems in Engineering, 2020
- Influence of Flange on Seismic Performance of 1,100‐kV Ultra‐High Voltage Transformer BushingEarthquake Spectra, 2019
- Evaluation of power substation equipment seismic vulnerability by multivariate fragility analysis: A case study on a 420 kV circuit breakerSoil Dynamics and Earthquake Engineering, 2017
- Seismic failure probability of a 400kV power transformer using analytical fragility curvesEngineering Failure Analysis, 2016
- Study of seismic response and vibration control of High voltage electrical equipment damper based on TMDIOP Conference Series: Materials Science and Engineering, 2016
- Chile Earthquake of 20102013
- Earthquake effects on SDG&E's 500/230kV Imperial Valley Substation2012
- Analysis and design of the prototype of a steel 1-MW wind turbine towerEngineering Structures, 2003
- Analysis of dynamic characteristics of structural joints using stiffness influence coefficientsKSME International Journal, 2000