Study on constraints for harmonic source determination using active power direction
- 26 April 2018
- journal article
- research article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Power Delivery
- Vol. 33 (08858977) , 1
Abstract
The traditional active power direction (APD) method has been proven to be unreliable to determine the dominant harmonic source at a point of common coupling (PCC), when both sides have the harmonic sources. In view of this shortcoming, this paper proposes an improved APD by imposing certain constraints to the traditional one. The constraints are developed based on the voltage and current measurements at the PCC and the impedance properties of the two sides. Through rigorous mathematical analysis, it has been proven that when those constraints are satisfied, the improved APD method is guaranteed to provide accurate results. Performance and effectiveness of the proposed method are demonstrated through simulation and field case verifications.Keywords
Funding Information
- Science and Technology Department of Sichuan Province Project (2017HH0081)
- National Natural Science Foundation of China (51477105)
This publication has 17 references indexed in Scilit:
- Method for determining utility and consumer harmonic contributions based on complex independent component analysisIET Generation, Transmission & Distribution, 2016
- A Novel Method for Noninvasive Estimation of Utility Harmonic Impedance Based on Complex Independent Component AnalysisIEEE Transactions on Power Delivery, 2015
- A “Critical Impedance”-Based Method for Identifying Harmonic SourcesIEEE Transactions on Power Delivery, 2004
- An investigation on the validity of power-direction method for harmonic source determinationIEEE Transactions on Power Delivery, 2003
- A method for determining customer and utility harmonic contributions at the point of common couplingIEEE Transactions on Power Delivery, 2000
- A Norton approach to distribution network modeling for harmonic studiesIEEE Transactions on Power Delivery, 1999
- On techniques for localization of sources producing distortion in three‐phase networksEuropean Transactions on Electrical Power, 1996
- A new method of harmonic power detection based on the instantaneous active power in three-phase circuitsIEEE Transactions on Power Delivery, 1995
- On the assessment of harmonic pollution [of power systems]IEEE Transactions on Power Delivery, 1995
- Harmonic power flow analysis for the measurement of the electric power qualityIEEE Transactions on Instrumentation and Measurement, 1995