Power Frequency Interference and Suppression in Measurement of Power Transmission Tower Grounding Resistance
Authors:
- 25 November 2014
- journal article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Power Delivery
- Vol. 30 (2) , 1016-1023
Abstract
Due to the electromagnetic induction between transmission lines and the associated grounding wires, power frequency current causes flow into the ground network via the metallic tower, which may interfere with grounding resistance measurements. This paper analyzes the mechanisms of this interference, and shows that power frequency interference becomes stronger at phase-wire transposition towers. Grounding resistance measurement by the variable frequency (VF) method has been proven to be effective in dealing with power frequency interference. However, the test equipment based on the VF method is always deactivated when the external interference voltage exceeds a preset level in order to avoid false readings. This paper aims at tackling the problem by introducing a reverse phase cancellation (RPC) method, which acquires and processes the interference signal before generating a cancelling signal with the same amplitude and frequency and a phase which is exactly opposite in polarity. This paper proves that the RPC method represents an excellent improvement over the VF method since it retains the advantages of VF and avoids the trip-out of test equipment due to excessive interference.Keywords
Funding Information
- National Natural Science Foundation of China
This publication has 21 references indexed in Scilit:
- Study of EHV Power Grid Over-voltage Monitoring system based on Rogow ski coil2011
- Transient Voltages in Transmission Lines Caused by Direct Lightning StrikesIEEE Transactions on Power Delivery, 2005
- Time domain analysis of grounding electrodes impulse responseIEEE Transactions on Power Delivery, 2003
- Practical method for evaluating ground fault current distribution in station, towers and ground wireIEEE Transactions on Power Delivery, 1998
- Energy absorption of surge arresters on power distribution lines due to direct lightning strokes-effects of an overhead ground wire and installation position of surge arrestersIEEE Transactions on Power Delivery, 1997
- The Open Loop Scheme: An Effective Method of Ground Wire Loss ReductionIEEE Transactions on Power Apparatus and Systems, 1984
- Measurements and Computations of Fault Current Distribution on Overhead Transmission LinesIEEE Transactions on Power Apparatus and Systems, 1984
- A Practical Ground Potential Rise Prediction Technique for Power StationsIEEE Transactions on Power Apparatus and Systems, 1980
- Field measurements and calculations of electrostatic effects of overhead transmission linesIEEE Transactions on Power Apparatus and Systems, 1976
- Transient analysis of underground power-transmission systems. System-model and wave-propagation characteristicsProceedings of the Institution of Electrical Engineers, 1973