Study on PD detection method in GIS under oscillating impulse voltage based on UHF method
Authors:
- 1 May 2017
- conference paper
- Published by Institute of Electrical and Electronics Engineers (IEEE)
- p. 305-308
Abstract
In order to ensure the safe operation of the gas insulated switchgear (GIS), on-site impulse withstand voltage test is becoming more and more important. Oscillating impulse voltage (OIV) is very suitable for the test due to its high efficiency. By detecting the partial discharge (PD) when conducting on-site impulse withstand voltage test, the insulation state of GIS can be known overall. The pulse current, ultrasonic, and ultra high frequency (UHF) are the mainly PD detection methods up to now. Among them, the UHF method is the most suitable method to detect the PD under OIV. However, there are electromagnetic interference signals generated by the impulse voltage generator which will influence the UHF detection results during the on-site impulse withstand voltage test. In this paper, the interference signals for the PD detection using UHF methods are analyzed. Based on this, an interference elimination method by using multiple UHF sensors for PD detection under OIV is introduced. This method is tested both in a lab environment and in field. The analyses show the interference signals for the PD detection using UHF methods under OIV is mainly related to the sphere-gap switch of impulse voltage generator. The results of lab experiments and field tests both show that the interference elimination method by using multiple UHF sensors is suitable for the PD detection under oscillating impulse voltage.Keywords
This publication has 7 references indexed in Scilit:
- Features Extraction and Mechanism Analysis of Partial Discharge Development under Protrusion DefectJournal of Electrical Engineering & Technology, 2015
- Partial discharge characteristics over SF6/epoxy interfaces under impulse voltageIEEE Transactions on Dielectrics and Electrical Insulation, 2013
- Analysis of the intrinsic characteristics of the partial discharge induced by typical defects in GISIEEE Transactions on Dielectrics and Electrical Insulation, 2013
- Characteristics and Development Mechanisms of Partial Discharge in SF6 Gas Under Impulse VoltagesIEEE Transactions on Plasma Science, 2011
- UHF technique for identification of partial discharge in a composite insulation under AC and DC voltagesIEEE Transactions on Dielectrics and Electrical Insulation, 2008
- Study on characteristic of partial discharge under DC condition2005
- GIS insulation co-ordination: on-site tests and dielectric diagnostic techniques. A utility point of viewIEEE Transactions on Power Delivery, 1996