A New Wide Area Protection Scheme Based on the Phase Angles of the Sequence Components
- 16 March 2021
- journal article
- research article
- Published by Taylor & Francis in Electric Power Components and Systems
- Vol. 49 (4-5) , 504-516
Abstract
— Several types of faults may occur in an active distribution network (ADN) such as single phase to ground, phase to phase, double phase to ground and three phases to ground faults. Many methods for the detection of all these faults are proposed in literature. However, the detection of open conductor faults is still a challenging task in distribution networks. These types of faults appear as a High Impedance Fault (HIF). This paper proposes a wide area protection scheme for radial ADN based on fault current component analysis. The proposed scheme uses the difference in the angles of the positive and negative sequence of the fault current between the main feeders and the branches of a radial ADN. The main feature of the proposed scheme is the ability to identify the faulted feeder even at HIF condition. Moreover, the proposed scheme can identify the faulty area along the faulty feeder. The effectiveness of the proposed technique is tested, using MATLAB/Simulink. Different scenarios are considered with various fault types including the open conductor faults. Simulation results demonstrate the effectiveness of the proposed scheme.Keywords
This publication has 23 references indexed in Scilit:
- An Integrated Wide-Area Protection Scheme for Active Distribution Networks Based on Fault Components PrincipleIEEE Transactions on Smart Grid, 2017
- Reliability Studies of Modern Distribution Systems Integrated With Renewable Generation and Parking LotsIEEE Transactions on Sustainable Energy, 2016
- Flexible Frequency Operation Strategy of Power System With High Renewable PenetrationIEEE Transactions on Sustainable Energy, 2016
- A Comprehensive Digital Protection Scheme for Low-Voltage Microgrids with Inverter-Based and Conventional Distributed GenerationsIEEE Transactions on Power Delivery, 2016
- Protection Coordination for Microgrids With Grid-Connected and Islanded Capabilities Using Communication Assisted Dual Setting Directional Overcurrent RelaysIEEE Transactions on Smart Grid, 2016
- Wide-area protection scheme for active distribution networks based on phase comparison2015
- A Communication-Assisted Protection Strategy for Inverter-Based Medium-Voltage MicrogridsIEEE Transactions on Smart Grid, 2012
- A Novel Back Up Wide Area Protection Technique for Power Transmission Grids Using Phasor Measurement UnitIEEE Transactions on Power Delivery, 2009
- Fault Direction Estimation in Radial Distribution System Using Phase Change in Sequence CurrentIEEE Transactions on Power Delivery, 2007
- Power System Blackouts: Analysis and Simulation of August 9, 2004 Blackout in Jordan Power SystemInformation Technology Journal, 2006