Numerical and Experimental Study of the Effect of Underfloor Blockages on Data Center Performance
Authors:
- 1 March 2011
- journal article
- Published by ASME International in Journal of Electronic Packaging
- Vol. 133 (1) , 011007
Abstract
Due to the increase in computer rack equipment power in recent years, thermal management of data centers has become a challenging problem. Data center facilities with raised floor plenums are the most popular configuration from a thermal management perspective. Considerable ongoing research efforts focus on optimizing the room layouts and equipment design in order to achieve the desired cooling. However, the detrimental impact of underfloor blockages, which occur widely, is seldom addressed. These blockages often take the form of chiller pipes, cabling, and wires. They impede the flow of cold air from the air conditioning units and yield unpredictable and undesirable air flow patterns. In this paper the effect of such underfloor blockages on data center performance is characterized in detail. A representative data center is modeled using a commercial computational fluid dynamics code with typical underfloor blockages. Blockages are shown to have a significant impact on tile flow rates and rack inlet temperatures. Based on the detailed numerical study broad guidelines are presented on managing the underfloor blockages for improved data center performance. Established guidelines are experimentally validated on a different data center cell. A detailed comparison between the experimental and numerical results is presented. Based on the numerical and experimental study it is concluded that blockages if placed in “critical” path can potentially have a detrimental impact on data center performance. Case studies are presented where blockages in “safe” path will have a minimum effect on data center performance.Keywords
This publication has 9 references indexed in Scilit:
- Experimental Investigation of the Impact of Under Floor Blockages on Flow Distribution in a Data Center Cell2007
- Effect of Under Floor Blockages on Data Center Performance2006
- Optimization of Data Center Room Layout to Minimize Rack Inlet Air TemperatureJournal of Electronic Packaging, 2006
- Experimental-Numerical Comparison for a High-Density Data Center: Hot Spot Heat Fluxes in Excess of 500 W/FT22006
- Guidelines on Managing Under Floor Blockages for Improved Data Center Performance2006
- Numerical Modeling of Data Center Clusters: Impact of Model Complexity2006
- Distributed Leakage Flow in Raised-Floor Data Centers2005
- Use of Computational Fluid Dynamics for Calculating Flow Rates Through Perforated Tiles in Raised-Floor Data CentersHVAC&R Research, 2003
- Techniques for Controlling Airflow Distribution in Raised-Floor Data Centers2003