Abstract
Arc faults in DC microgrids or photovoltaic (PV) systems are difficult to detect and isolate. Especially in location research, there are few related results, and arc fault detection is immature. This paper proposes a planar location method that requires only two detection points. Because the height of many DC systems is much smaller than their horizontal dimension, an antenna array and a fault source form a horizontal triangle to locate DC arc faults. Then, signal pulses are distinguished and extracted using a cross-correlation technique. A neural network (NN) and received signal strength indicators (RSSIs) are utilized to estimate the arc distance. However, the data from the dual detection points are insufficient for meeting the demands of NN training and may lead to a large location error. Therefore, a data-augmented neural network (DANN) technique was introduced into the algorithm to enhance the accuracy and robustness of distance estimation. The experimental verification results show that the method can effectively locate faults under a variety of arcing conditions. Moreover, the proposed method has intrinsic immunity to normal current fluctuations (NCFs). It can be used in PV plants or smart buildings with solar cells to avoid nuisance trips and improve the effectiveness of fault protection.
Funding Information
  • China Scholarship Council (201806705021)
  • National Natural Science Foundation of China (51607055, 51907047)
  • Public Projects of Zhejiang Province (GG20E070008)

This publication has 54 references indexed in Scilit: