This paper explains the principles of negative-sequence differential (87Q) protection, its basis for excellent sensitivity and speed, and the need for securing it with external fault detectors to deal with the saturation of current transformers. The paper reviews applications of 87Q elements to lines and transformers. It explains why 87Q elements cannot be used for turn-to-turn fault protection in shunt reactors and stators of generators and motors. The paper presents applications of negative-sequence directional elements for turn-to-turn fault protection in reactors and stators. Finally, it derives two new protection principles based on negative sequence for generator turn-to-turn fault protection.Keywords
This publication has 9 references indexed in Scilit:
- How to determine the effectiveness of generator differential protection2014
- Sizing current transformers for line protection applications2013
- Practical EHV reactor protection2013
- Percentage restrained differential, percentage of what?2011
- Fundamentals of short-circuit protection for transformers2010
- Principles of shunt capacitor bank application and protection2010
- Modern line current differential protection solutions2010
- Improvements in transformer protection and control2009
- AEP Experience With Protection of Three Delta/Hex Phase Angle Regulating Transformers2007