Detection and quantitative diagnosis of axial displacement of transformer winding by frequency response analysis
Open Access
- 16 July 2019
- journal article
- research article
- Published by Institution of Engineering and Technology (IET) in IET Generation, Transmission & Distribution
- Vol. 13 (15) , 3493-3500
Abstract
Transfer functions of a transformer whose winding is axially displaced are measured in several connection schemes of frequency response analysis (FRA), and the sensitivities of the measured transfer functions in these connection schemes to the axial displacement are evaluated. For the objective evaluation, some numerical indices are employed, and it is found that the inductive inter‐winding measurement is the most sensitive to the axial displacement. Furthermore, a simple circuit model is proposed to reproduce the measured transfer functions. All the parameters of the proposed circuit model can be determined from the measured transfer functions in FRA. The proposed model can also reproduce the measured transfer functions with the axial displacement by varying one parameter. The variation of the parameter in reproducing the transfer function with the axial displacement show good linear relation to the amount of the axial displacement. This indicates the possibility of a quantitative diagnosis of the axial displacement by FRA.Keywords
This publication has 20 references indexed in Scilit:
- Effect of Different Connection Schemes, Terminating Resistors and Measurement Impedances on the Sensitivity of the FRA MethodIEEE Transactions on Power Delivery, 2016
- Diagnostic Measurements for Power TransformersEnergies, 2016
- Improved power transformer winding fault detection using FRA diagnostics – part 1: axial displacement simulationIEEE Transactions on Dielectrics and Electrical Insulation, 2015
- Mathematical Comparison Methods to Assess Transfer Functions of Transformers to Detect Different Types of Mechanical FaultsIEEE Transactions on Power Delivery, 2010
- Determination of axial displacement extent based on transformer winding transfer function estimation using vector‐fitting methodEuropean Transactions on Electrical Power, 2007
- Design of Equivalent Circuits and Characterization Strategy for $n$-Input Coupled InductorsIEEE Transactions on Industry Applications, 2007
- Winding movement in power transformers: a comparison of FRA measurement connection methodsIEEE Transactions on Dielectrics and Electrical Insulation, 2006
- A Transfer Voltage Simulation Method for Generator Step Up TransformersIEEJ Transactions on Power and Energy, 2005
- Procedures for Detecting Winding Displacements in Power Transformers by the Transfer Function MethodIEEE Transactions on Power Delivery, 2004
- Transfer function method to diagnose axial displacement and radial deformation of transformer windingsIEEE Transactions on Power Delivery, 2003