Two Models for Predicting Frequency-Domain Spectroscopy of Nonuniformly Damped OIP Bushings Based on FEM and Dielectric Theory
- 18 April 2024
- journal article
- research article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Instrumentation and Measurement
- Vol. 73 (00189456) , 1-10
Abstract
Frequency-domain spectroscopy (FDS) is a nondestructive technique for moisture status evaluation of oil-impregnated paper (OIP) bushings; however, due to the lack of effective models to predict the FDS curve of OIP bushings under nonuniform moisture, it is difficult to establish a large database for FDS characteristics analysis and heterogeneous moisture status assessment. To address this issue, this article established a bushing finite element method (FEM) model and an improved X model based on the FEM and dielectric theory, respectively, for FDS prediction of nonuniformly damped OIP bushings. Comparing the FDS curves predicted by the bushing FEM model and the improved X model, it was found that the average relative errors are less than 1.25%. Finally, FDS measurements were conducted on the nonuniformly damped bushings in the laboratory to verify the accuracy of the proposed models. The experimental results indicated that the average relative errors of the bushing FEM model and improved X model in FDS prediction are less than 9.29% and 10.21%, respectively. This proves that the proposed models are highly accurate. The innovation of this article lies in establishing a bushing FEM model and an improved X model to predict the FDS curve of OIP bushings under nonuniform moisture.Keywords
Funding Information
- National Natural Science Foundation of China (52277138)
This publication has 32 references indexed in Scilit:
- Photon counting technique as a potential tool in micro‐defect detection of epoxy insulation pull rod in gas‐insulated switchgearsHigh Voltage, 2023
- A modified XY model of transformer oil–paper insulation system including non‐uniform aging and conductance effectIET Generation, Transmission & Distribution, 2021
- Fault diagnosis of the bushing infrared images based on mask R‐CNN and improved PCNN joint algorithmHigh Voltage, 2020
- Frequency Domain Spectroscopy for Non-Uniformly Distributed Moisture Detection in Transformer BushingsIEEE Access, 2020
- Modified Expression of Moisture Diffusion Factor for Non-Oil-Immersed Insulation PaperIEEE Access, 2019
- IEEE Guide for Dielectric Frequency Response Test2018
- Study on FDS characteristics of oil‐immersed paper insulation bushing under non‐uniform moisture contentIET Science, Measurement & Technology, 2018
- Quantitative diagnosis of moisture content in oil‐paper condenser bushing insulation based on frequency domain spectroscopy and polarisation and depolarisation currentIET Generation, Transmission & Distribution, 2017
- A dielectric frequency response model to evaluate the moisture content within an oil impregnated paper condenser bushingIET Science, Measurement & Technology, 2013
- Moisture equilibrium in paper-oil insulation systems1983