A field study of occupant controlled lighting in offices
Authors:
- 1 September 2002
- journal article
- research article
- Published by SAGE Publications in Lighting Research & Technology
- Vol. 34 (3) , 191-202
Abstract
A study of 14 open-plan offices equipped with occupant controlled general lighting recorded achieved workstation lighting conditions at a number of times of the year. The results confirmed the occurrence of a wide range of workstation lighting levels, many significantly below CIBSE Code recommendations, with average electrical loadings due to lighting in the order of 55% of maximum. System con-figuration had a significant influence on luminaire output, illuminances and energy consumption. In general the lowest luminaire outputs were in buildings where the default reset level was to a low output, with the highest outputs being in buildings having high reset levels and large control groups. In addition locally sited control devices were associated with lower luminaire output.Keywords
This publication has 11 references indexed in Scilit:
- Dissatisfaction and office productivityFacilities, 1995
- Light, Circadian Rhythms, and Mood Disorders: A ReviewAnnals of Clinical Psychiatry, 1992
- Relative visual performance: A basis for applicationLighting Research & Technology, 1991
- Negative reactions to increases in perceived personal control.Journal of Personality and Social Psychology, 1989
- Analysis of work environment data from three army field stations1988
- Office worker response to lighting and daylighting issues in workspace environments: A pilot surveyEnergy and Buildings, 1984
- Light Suppresses Melatonin Secretion in HumansScience, 1980
- Consistency and variation in preferences for office lightingLighting Research & Technology, 1974
- Age, illuminance, visual performance and preferenceLighting Research & Technology, 1973
- Multidimensional Scaling of Luminous EnvironmentJournal of the Illuminating Engineering Society, 1973