The high penetration of renewable energy has posed significant challenges to frequency regulation, primarily due to the scarcity of traditional regulation resources in these regions. To address this, a novel secondary frequency regulation control method utilizing voltage-sensitive flexible load (VSFL) clusters is proposed. The strategy leverages the voltage-active power coupling characteristics of composite loads. By regulating the load voltage, composite loads under 110/10 kV substations are transformed into controllable loads, which are then aggregated to collaborate with Automatic Generation Control (AGC) units in SFR. To tackle the inherent uncertainty in load regulation capacity, a load control signal correction strategy based on Tube-based Model Predictive Control (T-MPC) is designed. This strategy effectively compensates for calculation errors in control objectives caused by load uncertainty, achieving optimal control with minimal cost. Simulation results demonstrate that the proposed scheme enables the large-scale mining and flexible utilization of load-side regulation resources. Furthermore, the T-MPC approach exhibits superior robustness and frequency regulation performance compared to traditional MPC methods.