Abstract
In this work a new single-ended method for fault location in distribution networks is proposed. The method is an active traveling wave fault location, which transmits a Gaussian chirp through the line and applies the cross time-frequency reflectometry in order to find the exact location of the fault with 150 meter tolerance. The method functions in the offline post fault condition, where the system is disconnected. The bandwidth of the proposed method is at least one order of magnitude smaller than its passive counterparts. Furthermore, not only is the method capable of locating the exact distance of the fault away from the relay location, but it also finds the exact line in radial configuration of distribution network. Another characteristics of this method is its immunity to series capacitive compensated transmission line, voltage level, fault phase, fault inception angle, and fault resistance. Another important property of the method is its ability in locating high impedance faults. The method capabilities are verified using PSCAD/EMTDC simulation based on phase-dependent and frequency-dependent models for distribution network lines. An error parameter is defined to compare the method efficiency for different fault types, fault locations, and system configurations.Keywords
This publication has 30 references indexed in Scilit:
- Fault location based on single terminal travelling wave analysis in radial distribution networkInternational Journal of Electrical Power & Energy Systems, 2015
- High impedance fault detection method efficiency: Simulation vs. real-world data acquisition2015
- DT-CWT based event feature extraction for high impedance faults detection in distribution systemInternational Transactions on Electrical Energy Systems, 2014
- High-Impedance Faulted Branch Identification Using Magnetic-Field Signature AnalysisIEEE Transactions on Power Delivery, 2012
- Universal Wavefront Positioning Correction Method on Traveling-Wave-Based Fault-Location AlgorithmsIEEE Transactions on Power Delivery, 2012
- High impedance fault detection using combination of multi-layer perceptron neural networks based on multi-resolution morphological gradient features of current waveformIET Generation, Transmission & Distribution, 2011
- Evaluation and performance comparison of power swing detection algorithms in presence of series compensation on transmission lines2011
- Simulation of high impedance ground fault In electrical power distribution systems2010
- High-Impedance Fault Detection in Distribution Networks With Use of Wavelet-Based AlgorithmIEEE Transactions on Power Delivery, 2006
- High Impedance Fault Detection Based on Wavelet Transform and Statistical Pattern RecognitionIEEE Transactions on Power Delivery, 2005