Verifying interoperability and application performance of PMUs and PMU-enabled IEDs
Authors:
- 1 July 2012
- conference paper
- Published by Institute of Electrical and Electronics Engineers (IEEE)
- p. 1-7
Abstract
This paper presents a new test methodology for verifying the interoperability and application performance of PMUs and PMU-enabled IEDs at the device and system level. Two types of tests are defined to evaluate the performance of synchrophasor devices from two different aspects: design and application. The interoperability between PMUs, time synchronization options, and phasor data concentrators (PDCs) can be verified by design test methodology. A fault location algorithm using two-end synchronized measurements is used to evaluate the application performance. A reference PMU algorithm and synchrophasor system test set-up have been developed to perform the tests. Nine commercial PMUs and four GPS receivers with different synchronization options are selected to perform the tests. The test results are summarized at the end.Keywords
This publication has 16 references indexed in Scilit:
- Calculating combined amplitude and phase modulated power signal parameters2011
- Characterizing dynamic behavior of PMUs using step signalsEuropean Transactions on Electrical Power, 2010
- Testing of Phasor Measurement Units2010
- Setup of the laboratory for Synchronized Measurement for PMU's testing2009
- Performance evaluation of phasor measurement systems2008
- Practical Experience with PMU System Testing and Calibration Requirements2008
- Progresses in PMU testing and calibration2008
- Testing phasor measurement units2008
- Calibration and testing of TESLA Phasor Measurement Unit (PMU) using doble F6150 test instrument2007
- Comparative testing of synchronized phasor measurement units2004