Soil ionisation under lightning impulse voltages
- 4 September 2004
- journal article
- Published by Institution of Engineering and Technology (IET) in IEE Proceedings - Science, Measurement and Technology
- Vol. 151 (5) , 343-346
Abstract
Experiments have been carried out to study soil ionisation and the variation of the critical ionisation gradient against the soil resistivity. Compared with relevant experimental results of other researchers a satisfactory convergence has been proved. An accurate estimation of the critical ionisation gradient has been achieved, of the order of 200 kV/m, following the finding that the critical voltage gradient for wet soil decreases to approximately 35% of the corresponding value for dry soil.Keywords
This publication has 8 references indexed in Scilit:
- The soil ionization gradient associated with discharge of high currents into concentrated electrodesIEEE Transactions on Power Delivery, 1994
- Estimating lightning performance of transmission lines. II. Updates to analytical modelsIEEE Transactions on Power Delivery, 1993
- Lightning surge response of ground electrodesIEEE Transactions on Power Delivery, 1989
- A new general estimation curve for predicting the impulse impedance of concentrated earth electrodesIEEE Transactions on Power Delivery, 1988
- Electrical Breakdown Characteristics of SoilIEEE Transactions on Nuclear Science, 1982
- Experimental Study of Transient Ground ImpedancesIEEE Transactions on Power Apparatus and Systems, 1981
- Impulse and Alternating Current Tests on Grounding Electrodes in Soil EnvironmentIEEE Transactions on Power Apparatus and Systems, 1978
- Dynamic model of impulse characteristics of concentrated earthsProceedings of the Institution of Electrical Engineers, 1974