Abstract
Simplified weak grid models are widely used to emulate the non-ideal power grid for the design and stability analysis of grid-connected inverters. However, the dynamic behavior of a real grid with multiple inverters is complex. In this paper, an emulation method is proposed for multi-inverter integrated weak grids using an interaction-preserved aggregation model associated with grid impedance. Firstly, the interaction among inverters in weak grids is analyzed using the state-space model and participation analysis. Then, two-inverter aggregation is proposed for a large-scale system. This model can preserve the impact of parameters on the interaction modes (IMs), and predict the IM-related instability of multi-inverter systems. Thus, the two-inverter representation is applied to emulation to preserve interactions and to simplify the testing of multiple inverters. The emulation of the 16-inverter system is implemented on a hardware-in-the-loop (HIL) test bench with one practical inverter controller under test and remaining parts integrated in the OPAL-RT real-time simulator. The test results show that the instability attributed to interaction can be identified by the proposed emulation method.
Funding Information
  • National Natural Science Foundation of China (51637007, 51877159, U1866601)
  • VILLUM FONDEN under the VILLUM Investigator (25920)
  • Center for Research on Microgrids
  • Villum Investigator from The Villum Foundation (999730)

This publication has 25 references indexed in Scilit: