SF 6 breakdown in GIS
Authors:
- 4 September 1996
- journal article
- Published by Institution of Engineering and Technology (IET) in IEE Proceedings - Science, Measurement and Technology
- Vol. 143 (5) , 270-276
Abstract
SF6 gas breakdown and spacer surface flashover volt–time characteristic curves were established for a GIS of D/d = 55/25 (15 mm gap) and D/d = 45/25 (10 mm gap) for 1.2/50, 0.5/50, 0.2/50 and osc/50 (1.64 MHz) µs impulse and disconnector induced VFT voltages. VFT volt–time curves established using actual breakdown voltages against actual time to breakdown were found to give a better representation of the dielectric performance, and thus are recommended for future applications. Highly inhomogeneous field geometries, such as particle contaminated gaps, caused downward turning of the v–t curves during VFT breakdowns at short times to breakdown.Keywords
This publication has 3 references indexed in Scilit:
- Inhomogeneous field breakdown in GIS-the prediction of breakdown probabilities and voltages. I. Overview of a theory for inhomogeneous field breakdown in SF/sub 6/IEEE Transactions on Power Delivery, 1988
- The generalized integration method for predicting impulse volt-time characteristics for non-standard wave shapes-a theoretical basisIEEE Transactions on Electrical Insulation, 1988
- VOLT-TIME CURVES OF DISCONNECTOR-GENERATED FAST TRANSIENTS INSIDE GIS1987