SF 6 breakdown in GIS

Authors:

Abstract
SF6 gas breakdown and spacer surface flashover volt–time characteristic curves were established for a GIS of D/d = 55/25 (15 mm gap) and D/d = 45/25 (10 mm gap) for 1.2/50, 0.5/50, 0.2/50 and osc/50 (1.64 MHz) µs impulse and disconnector induced VFT voltages. VFT volt–time curves established using actual breakdown voltages against actual time to breakdown were found to give a better representation of the dielectric performance, and thus are recommended for future applications. Highly inhomogeneous field geometries, such as particle contaminated gaps, caused downward turning of the v–t curves during VFT breakdowns at short times to breakdown.