Mold Contamination and Air Handling Units
Authors:
- 21 May 2007
- journal article
- research article
- Published by Taylor & Francis in Journal of Occupational and Environmental Hygiene
- Vol. 4 (7) , 483-491
Abstract
An investigation was conducted on selected locations in air handling units (AHUs) to (a) identify common mold species found on these locations, (b) determine whether some locations (and subsets) featured mold growth sites more frequently than others, (c) ascertain whether the operating condition of AHUs is related to mold contamination, and (d) provide a basis for a microbial sampling protocol for AHUs. A total of 566 tape lifts and 570 swab samples were collected from the blower wheel fan blades, insulation, cooling coil fins, and ductwork from 25 AHUs. All AHU conditions were numerically rated using a heating, ventilation and air-conditioning (HVAC) survey. Results showed that Cladosporium sp. fungi were commonly recovered in terms of growth sites and deposited spores, and they were found mainly in the blower wheel fan blades, the ductwork, and the cooling coil fins. Subsections of the fan blades, insulation, and cooling coil fins showed no preferred area for mold growth sites. Other organisms such as Penicillium sp., Aspergillus sp., and Paecilomyces sp. were recovered from the cooling coil fins and insulation. Because of the widespread prevalence of Cladosporium sp., there was no relationship between mold growth and operating condition. However, the presence of different species of molds in locations other than the blower wheel blades may indicate that the AHU condition is not optimal. A suggested microbial sampling protocol including interpretations of sample results is presented.Keywords
This publication has 8 references indexed in Scilit:
- Mold colonization during use of preservative-treated and untreated air filters, including HEPA filters from hospitals and commercial locations over an 8-year period (1996–2003)Journal of Industrial Microbiology and Biotechnology, 2005
- Measuring environmental fungal exposureMedical Mycology, 2005
- Culturability and Toxicity of Sick Building Syndrome-Related Fungi Over TimeJournal of Occupational and Environmental Hygiene, 2004
- An Investigation into Techniques for Cleaning Mold-Contaminated Home ContentsJournal of Occupational and Environmental Hygiene, 2004
- Growth of Mold on Fiberglass Insulation Building Materials—A Review of the LiteratureJournal of Occupational and Environmental Hygiene, 2004
- Capability of air filters to retain airborne bacteria and molds in heating, ventilating and air-conditioning (HVAC) systemsInternational Journal of Hygiene and Environmental Health, 2001
- Resolution of Sick Building Syndrome in a High-Security FacilityApplied Occupational and Environmental Hygiene, 2000
- Correlation between the prevalence of certain fungi and sick building syndrome.Occupational and Environmental Medicine, 1998