Effect of supply voltage asymmetry on IRP p – q -based switching compensator control
Author:
- 1 January 2010
- journal article
- Published by Institution of Engineering and Technology (IET) in IET Power Electronics
- Vol. 3 (1) , 11-17
Abstract
Results of a study on how the supply voltage asymmetry affects the reference signal for switching compensator control, in a situation when this signal is generated using the instantaneous reactive power (IRP) p–q theory are presented. According to the IRP p–q approach, the compensator should compensate IRP and the alternating component of the instantaneous active power of the load. However, that in the presence of the supply voltage asymmetry, even an ideal, unity power factor load has an instantaneous active power with a non-zero alternating component is demonstrated. According to IRP p–q theory-based approach, it should be compensated and this requires that a distorted current be injected into the distribution system. It means that in the presence of the supply voltage asymmetry, the algorithms based on the IRP p–q theory generate a non-sinusoidal reference signal for the compensator control, even when voltages and currents in the system are sinusoidal.Keywords
This publication has 13 references indexed in Scilit:
- Development of a Network-Wide Harmonic Control Scheme Using an Active FilterIEEE Transactions on Power Delivery, 2007
- An Improved Control Algorithm for Active FiltersIEEE Transactions on Power Delivery, 2007
- Instantaneous Reactive Power Theory: A Comparative Evaluation of Different FormulationsIEEE Transactions on Power Delivery, 2006
- A universal reference current generating method for active power filter2004
- On Some Misinterpretations of the Instantaneous Reactive Power$phbox-q$TheoryIEEE Transactions on Power Electronics, 2004
- On the compensation of non‐active current components of three‐phase loads with quickly changing unsymmetryEuropean Transactions on Electrical Power, 2001
- An optimal and flexible control strategy for active filtering and power factor correction under non-sinusoidal line voltagesIEEE Transactions on Power Delivery, 2001
- Application of running quantities for control of an adaptive hybrid compensatorEuropean Transactions on Electrical Power, 1996
- Dynamic compensation of non‐active power using the fbd method ‐ basic properties demonstrated by benchmark examplesEuropean Transactions on Electrical Power, 1994
- Instantaneous Reactive Power Compensators Comprising Switching Devices without Energy Storage ComponentsIEEE Transactions on Industry Applications, 1984