Insulation coordination study for a 50 kV traction feeder station
Authors:
- 1 September 2014
- conference paper
- Published by Institute of Electrical and Electronics Engineers (IEEE)
- p. 1-6
Abstract
The heavy haul rail network in Queensland Australia generally adopts a lightning impulse withstand voltage rating of 250 kV for the switchgear and autotransformers within its 50 kV ac traction feeder stations. The aging switchgear across a number of feeder stations in this network are undergoing upgrade and the rail network operator is considering the possibility of using 200 kV rating for the upgraded switchgear. This paper investigates the lightning over-voltages that could occur at the feeder stations under review. Fast front transient models of the feeder stations and the associated traction corridors are developed in PSCAD/EMTDC software. Simulations are conducted to evaluate the likely over-voltages under various scenarios and the results are presented. Finally, the required lightning impulse withstand voltage rating for the switchgear is determined based on the simulation results.Keywords
This publication has 5 references indexed in Scilit:
- Distribution of the Traction Return Current in AT Electric Railway SystemsIEEE Transactions on Power Delivery, 2005
- Parameter Determination for Modeling System Transients—Part I: Overhead Lines IEEE PES Task Force on Data for Modeling System Transients of IEEE PES Working Group on Modeling and Analysis of System Transients Using Digital Simulation (General Systems Subcommittee)IEEE Transactions on Power Delivery, 2005
- A Method of a Lightning Surge Analysis Recommended in Japan Using EMTPIEEE Transactions on Power Delivery, 2005
- Modeling guidelines for fast front transientsIEEE Transactions on Power Delivery, 1996
- A high frequency transformer model for the EMTPIEEE Transactions on Power Delivery, 1993