Real-Time PD Identification in Diagnosis of GIS Using Symmetric and Asymmetric UHF Sensors
Authors:
- 28 June 2004
- journal article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Power Delivery
- Vol. 19 (3) , 1072-1077
Abstract
A new practical method for real-time insulation diagnosis of gas-insulated switchgear (GIS) has been developed and introduced. A notable technique, which takes the output ratio of a symmetric ultra-high-frequency (UHF) sensor (e.g., a loop electrode) to an asymmetric one (e.g., a conical coupler), makes it possible to immediately identify defects and also to eliminate noises because the output ratio of those UHF sensors strongly depends on the radial position of the GIS. It would be remarkably effective for dc power transmission, intermittent partial discharge (PD), and sequential risk assessment based on each identified PD pulse, which would support condition-based maintenance.Keywords
This publication has 6 references indexed in Scilit:
- PD signal propagation characteristics in GIS and its location system by frequency components comparisonIEEE Transactions on Power Delivery, 2001
- The application of ultra-high-frequency partial discharge measurements to gas-insulated substationsIEEE Transactions on Power Delivery, 1998
- Study on an after-laying test for a long-distance GILIEEE Transactions on Power Delivery, 1998
- Pattern analysis of partial discharges in SF/sub 6/ GISIEEE Transactions on Dielectrics and Electrical Insulation, 1998
- The excitation of UHF signals by partial discharges in GISIEEE Transactions on Dielectrics and Electrical Insulation, 1996
- Detection of parallel discharges in gas insulated substationsIEEE Transactions on Power Delivery, 1992