Insulation modelling for thermal FEM analysis of PVC and XLPE cables under fault conditions
- 23 September 2011
- journal article
- research article
- Published by Wiley in European Transactions on Electrical Power
- Vol. 22 (8) , 1093-1111
Abstract
SUMMARY: An approach to modelling of electrical and thermo‐physical properties in small cylindrical volumes of cable insulation, that is, insulation spot samples is presented in this paper. Apart from small leakage currents, high currents can flow through these spots under fault conditions, at the same time heating up and destroying the cable insulation in them as well. An introduction of models for electrical and thermo‐physical properties of the insulation to the nonlinear thermal finite element method (FEM) analysis of faults is demonstrated on the examples of short circuits that occurred in buried power cables. Nonlinearity of the thermal FEM model is based on the heat sources, electrical and thermo‐physical properties of polyvinyl‐chloride and cross‐linked polyethylene insulation as functions of temperature and/or time. According to the DIN VDE standards, the cable structures considered herein correspond to the NAYY 4×120 SM 0.6/1 kV and NA2XY 4×120 SM 0.6/1‐kV cables. The proposed models for insulation properties are applicable to the fault thermal FEM analysis of all multi‐core power cables laid in the soils, air or water. Copyright © 2011 John Wiley & Sons, Ltd.Keywords
This publication has 9 references indexed in Scilit:
- FEM modelling of faults occurred in buried power cables due to the removal of tree rootsEuropean Transactions on Electrical Power, 2010
- Identification of temperature-dependent thermal properties of solid materialsJournal of the Brazilian Society of Mechanical Sciences and Engineering, 2008
- Preparation of granular crosslinkable medium‐density polyethyleneJournal of Applied Polymer Science, 2007
- Current and Heat Transfer across the Contact Interface2006
- Controlling the thermal environment in hot spots of buried power cablesEuropean Transactions on Electrical Power, 2006
- Thermal degradation of PVC cable insulation studied by simultaneous TG-FTIR and TG-EGA methodsJournal of Thermal Analysis and Calorimetry, 2004
- Thermally Induced Failure of Low-Voltage Electrical Nonmetallic-Sheathed Cable InsulationFire Technology, 1999
- Electrical properties of silane crosslinked polyethylene in comparison with DCP crosslinked polyethyleneIEEE Transactions on Dielectrics and Electrical Insulation, 1999
- Mechanism for impulse conversion of water trees to electrical trees in XLPEIEEE Transactions on Power Delivery, 1998